Rental electrical safety checks in Victoria: what landlords and property managers need to know

In Victoria, rental providers must have a licensed or registered electrician check all electrical installations, fixtures and fittings every two years. Since 13 October 2026 this covers every rental property, not only leases from 29 March 2021. Keep the record, tell new renters the last check date, and supply a copy within 7 days of a written request.

This guide is general information, not legal advice. Rules change, so check the Consumer Affairs Victoria pages linked below or get advice for your own situation.

Which rental properties need an electrical safety check?

When the two-yearly check was introduced, it only applied to rental agreements entered into on or after 29 March 2021. That has now changed. Consumer Affairs Victoria’s new changes to rental laws page says that from 13 October 2026, rental providers must arrange gas and electrical safety checks by a qualified tradesperson every two years in all rental properties.

If you have an older lease that rolled onto a periodic agreement, the rule now applies to it too.

If no electrical safety check has been done in the two years before a renter moves in, the check must be completed as soon as possible (Consumer Affairs Victoria).

Who is allowed to do the check?

Only a licensed or registered electrician. Consumer Affairs Victoria and Energy Safe Victoria are both clear on this. A property manager, handyperson or owner cannot do it.

If the check turns up something that needs fixing, Energy Safe Victoria says the repair work should be done by a Registered Electrical Contractor (REC) or a licensed electrician employed by one (ESV electricians’ toolkit).

What does a rental electrical safety check cover?

The check covers all electrical switchboards, wiring, installations, fixtures and fittings at the property. According to Consumer Affairs Victoria, the inspection and testing must be done in line with section 4 of the Australian Standard AS/NZS 3019 (Electrical installations: Periodic assessment), with the report done in line with section 2 of that standard.

In plain terms, the electrician is checking whether the installation is still safe to use, not whether it matches brand new work. Anything unsafe or damaged should be listed in the report with recommended repairs. The section on our own checks further down lists what that looks like on site.

Electrician testing a switchboard before work

Electrician testing a switchboard at a Melbourne property

What records do landlords have to keep and give to renters?

Based on Consumer Affairs Victoria and Energy Safe Victoria guidance:

  • Keep the most recent record until a record of the next check is created.
  • Disclose before signing. Before entering into a rental agreement, you must tell the renter the date of the last electrical safety check and any outstanding recommendations from it.
  • Hand it over on request. If a renter asks in writing, you must give them a copy of the most recent check within 7 days.
  • Older leases. Renters on agreements that began before March 2021 can ask in writing for the date of the last check if they do not know it.

Energy Safe Victoria says the electrician’s record should include their full name, business details and licence number, the date of the check, the results, any repairs needed and action taken, and confirmation that everything was checked and found safe. ESV accepts its own Electrical Safety Check report, Form 1 from Appendix A of AS/NZS 3019:2022, or another report that includes the same details.

One common mix up: a Certificate of Electrical Safety (COES) is not the record for the safety check. A COES is issued when electrical work such as a repair is carried out (ESV).

Do rentals need safety switches (RCDs)?

Yes. Electrical safety has been a rental minimum standard since 29 March 2023. Consumer Affairs Victoria’s minimum standards page says rental properties must have modern switchboards with circuit breakers and electrical safety switches installed. Safety switches include RCDs, RCCBs and RCBOs.

At a minimum, the power point and lighting circuits must be protected by switchboard-type circuit breakers and safety switches. On an old ceramic fuse board, the whole switchboard may need replacing, and then every circuit needs circuit breaker protection.

A few related points from Consumer Affairs Victoria:

  • Since 25 November 2025, a property must meet the minimum standards when it is advertised, not just before the renter moves in. Advertising, offering or providing a property that does not meet the standards is an offence.
  • From 13 October 2026, all rental providers must keep records showing the property meets the minimum standards, and Consumer Affairs Victoria can ask to see them.
  • If a renter has signed but not moved in and the property does not meet the minimum standards, they can end the agreement immediately without fees (renters’ rights).

If your rental still has a fuse board, our switchboard upgrades and safety switch installation pages explain the work involved.

Old ceramic fuse board before replacement

Old ceramic fuse board without safety switches

What are the smoke alarm rules for rentals?

From 25 November 2025, rental providers and their agents must arrange annual smoke alarm safety checks for all rental agreements, whatever date the agreement started (Consumer Affairs Victoria).

Rental providers must make sure smoke alarms:

  • are correctly installed and in working order
  • are fitted with batteries or replacement batteries
  • are tested at least once every 12 months, following the manufacturer’s instructions.

Before the agreement starts, give the renter written information on how each alarm works and how to test it. Buildings constructed after 1 August 1997 must have hard-wired alarms with battery backup, and hard-wired alarms must be installed by a qualified electrician. Alarms must meet AS 3786.

If a renter tells you a smoke alarm is not working, it is an urgent repair and must be fixed or replaced immediately.

Many landlords line up every second smoke alarm check with the two-yearly electrical check. See our smoke alarm installation and repair page.

What about the gas safety check?

Where a property has gas appliances, fixtures or fittings, a separate gas safety check is also required every two years. It must be done by a licensed or registered gasfitter endorsed in Type A gas servicing, not an electrician (Consumer Affairs Victoria). Electrical Powerhaus does not do gas work, so you will need a gasfitter for that part.

What happens if an electrical fault comes up between checks?

A dangerous electrical fault, or the electricity supply not working, is an urgent repair under Victorian renting law. Smoke alarms and other safety devices that are not working are urgent repairs too (Consumer Affairs Victoria repairs page).

The rental provider must arrange urgent repairs immediately. If the renter cannot reach you, or you do not act straight away, the renter can arrange and pay for the urgent repair themselves. They then give you written notice with receipts, and you have 7 days to repay them. If you do not, they can go to Rental Dispute Resolution Victoria and then VCAT.

Property managers need an electrician who answers after hours. Our 24/7 emergency electrician service covers Melbourne.

Melted power point found in a property

Melted power point found and replaced by Electrical Powerhaus

What are the penalties for not doing the check?

The Consumer Affairs Victoria pages we checked do not list penalty amounts for missing the two-yearly check. They do make the practical exposure clear: renters can demand the record within 7 days, VCAT can order repairs, and advertising or providing a property that fails the minimum standards is an offence. For penalty amounts, see the Residential Tenancies Act 1997 or ask your lawyer.

Landlord and property manager checklist

  • Find the date of the last electrical safety check for each property. If it is over two years ago, or there is no record, book one now.
  • Book the annual smoke alarm check, and line it up with the electrical check every second year.
  • If the property has gas, book a separate gas safety check with a licensed gasfitter.
  • Confirm the switchboard has circuit breakers and safety switches protecting at least the power and lighting circuits.
  • Keep the most recent electrical and gas check records until the next ones replace them.
  • Keep records showing the property meets the minimum standards.
  • Before a new lease is signed, tell the renter the date of the last check and any outstanding recommendations.
  • Give renters a copy of the latest check within 7 days of a written request.
  • Fix any recommended repairs and keep the COES for that work.
  • Give renters an after-hours number for urgent repairs, and act on dangerous electrical faults immediately.

Rental safety obligations at a glance

CheckHow oftenWho can do itSource
Electrical safety checkEvery 2 years (all rental properties from 13 October 2026)Licensed or registered electricianCAV
Smoke alarm checkAt least every 12 months (all agreements from 25 November 2025)Not specified by CAV; hard-wired alarms installed by a qualified electricianCAV
Gas safety check (if gas is present)Every 2 yearsLicensed or registered gasfitter, Type A servicingCAV
Switchboard circuit breakers and safety switches (minimum standard)Must be met before the property is advertised or occupied (standard since 29 March 2023)ElectricianCAV
Copy of latest check to renterWithin 7 days of a written requestRental provider or agentCAV
Dangerous electrical faultUrgent repair, immediatelyREC or licensed electricianCAV

What does an Electrical Powerhaus rental safety check involve?

A licensed electrician from our team visits the property, with access arranged through you or your property manager. The check follows AS/NZS 3019 and in plain terms covers:

  • Switchboard: a look at the board’s condition and labelling, and a test of each safety switch to make sure it trips.
  • Power points and switches: checked for damage, heat marks and correct operation.
  • Light fittings: checked for damage, heat and secure mounting.
  • Visible wiring: checked for damage, perished insulation and unsafe old work.
  • Smoke alarms: tested at the same visit, so the annual smoke alarm check is done while we are there.
  • Written report: you get a written report in a format Energy Safe Victoria accepts, listing what was checked, the results and any recommended repairs. Keep it as your record and hand a copy to renters on request.

If we find something unsafe, we explain it and quote the repair. Any repair work we carry out comes with a Certificate of Electrical Safety for that work, which you keep alongside the check report.

To get a property ready, see our guide on how to prepare for an electrical inspection in Victoria and, for owner-occupied homes, our home electrical inspection guide.

New switchboard with safety switches

New switchboard with safety switches fitted

Book checks for one rental or a whole portfolio

Electrical Powerhaus works with Melbourne landlords and property managers on two-yearly electrical safety checks, smoke alarm checks and the repairs that come out of them. From a single investment property to a full rent roll, we book the checks across your portfolio, send each report straight to you for your records, and remind you when the next check is due, so no property slips past its two-year date.

New to Electrical Powerhaus? Your first service is 15% off. Landlords who are pensioners or seniors get 10% off every time. Rated 4.9 from 188 Google reviews.

Call 03 6358 2028 or book a rental electrical safety check, or see our electrical safety and compliance services.

FAQ

How often does a rental property need an electrical safety check in Victoria? Every two years. The check must be done by a licensed or registered electrician. From 13 October 2026 the rule applies to all rental properties, not only leases signed from 29 March 2021.

Does the two-yearly check apply to leases signed before March 2021? Yes, from 13 October 2026. Consumer Affairs Victoria says rental providers must arrange gas and electrical safety checks every two years in all rental properties.

Can a property manager do the electrical safety check? No. Only a licensed or registered electrician can do it. The property manager can arrange the check and keep the record.

What do I have to give my renter? Before the lease is signed, the date of the last electrical safety check and any outstanding recommendations. During the tenancy, a copy of the most recent check within 7 days of a written request.

Is a Certificate of Electrical Safety the same as a safety check report? No. Energy Safe Victoria says a COES is not the correct record for the safety check. A COES is issued when electrical work, such as a repair, is carried out.

How often do smoke alarms need checking in a rental? At least once every 12 months. From 25 November 2025 this applies to all rental agreements, whenever they started. A faulty smoke alarm is an urgent repair.